Local control panel – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 44

Advertising
background image

Parameter number

Description

Set to

8-53

Start Select

Determines the control location of the start

command. Set to Digital input to use a digital

input only. Set to Bus to use only the serial bus

only. Set to Logic AND to use the serial bus

AND a digital input. Set to Logic OR to use the

serial bus OR a digital input.

8-55

Set-up Select*

Determines the control location of the set-up

selection function. Set to Digital input to use a

digital input only. Set to Bus to use only the

serial bus only. Set to Logic AND to use the

serial bus AND a digital input. Set to Logic OR

to use the serial bus OR a digital input.

8-56

Preset Reference Select*

Determines the control location of the preset

reference selection function. Set to Digital

input to use a digital input only. Set to Bus to

use only the serial bus only. Set to Logic AND

to use the serial bus AND a digital input. Set to

Logic OR to use the serial bus OR a digital

input.

* The Set-up Select and Preset Reference Select functions are used to control other pre-
configured functions in the controller. To avoid interfering with these functions, it is
recommended to control this function via digital inputs.

Local control panel

The controller is equipped with a local control panel (LCP). The LCP combines the status
screen and keypad found on the front of the controller. The LCP is the user interface to the
controller. The LCP allows the user to perform various functions such as:

• Start, stop and control speed with the keypad when in local/Hand mode
• View and display the status of the controller, pump and system
• Provides access to all parameters and start up functions
• Manually reset the controller after a fault
• Perform parameter backup

Electrical Installation

42

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL