Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 136

Table 40: EN50178 fuses 200 V to 480 V
Frequency converter
Maximum fuse size
Voltage
Type
208–230 V — T2
0015–0020
16A
1)
200–240
type gG
0030
25A
1)
200–240
type gG
0050
35A
1)
200–240
type gG
0075
50A
1)
200–240
type gG
0100
63A
1)
200–240
type gG
0150
63A
1)
200–240
type gG
0200
80A
1)
200–240
type gG
0250
125A
1)
200–240
type gG
0300
125A
1)
200–240
type gG
0400
160A
1)
200–240
type gG
0500
200A
1)
200–240
type aR
0600
250A
1)
200–240
type aR
380–460 V — T4
0015–0020
10A
1)
380–500
type gG
0030
16A
1)
380–500
type gG
0050–0075
25A
1)
380–500
type gG
0100
35A
1)
380–500
type gG
0150–0200
63A
1)
380–500
type gG
0250
63A
1)
380–500
type gG
0300
63A
1)
380–500
type gG
0400
80A
1)
380–500
type gG
0500
100A
1)
380–500
type gG
0600
125A
1)
380–500
type gG
0750
160A
1)
380–500
type gG
1000
250A
1)
380–500
type aR
1250
250A
1)
380–500
type aR
1)
Maximum fuses see national/international regulations for selecting an applicable fuse
size.
Table 41: 525–690 V, Frame sizes A, C, D, E and F (non-UL fuses)
Enclosure size
Power [HP]
Current rating
Recommended
fuse size
Recommended
maximum fuse
Recommended
circuit breaker
Danfoss
Maximum trip
level [A]
A3
1.5
gG-6
gG-25
CTI25M 10–16
16
2
gG-6
gG-25
CTI25M 10–16
16
3
gG-6
gG-25
CTI25M 10–16
16
5
gG-10
gG-25
CTI25M 10–16
16
7.5
gG-16
gG-25
CTI25M 10–16
16
10
gG-16
gG-25
CTI25M 10–16
16
Technical Specification
134