Mechanical installation, Installation requirements – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 53

Advertising
background image

Mechanical Installation

Installation requirements

Cooling

• To provide cooling airflow, mount the unit to a solid flat surface or to the optional

back plate.

• Top and bottom clearance for air cooling must be provided. Generally, 100–225 mm

(4–10 in) is required.

a

b

Enclosure

A2–A5

B1–B4

C1, C3

C2, C4

a/b

100 mm (3.9 in)

200 mm (7.9 in)

200 mm (7.9 in)

225 mm (8.9 in)

• Improper mounting can result in overheating and reduced performance.
• Derating for temperatures starting between 40°C (104°F) and 50°C (122°F) and

elevation 1000 m (3300 ft) above sea level must be considered. See the Technical
Bulletin for detailed information.

Lifting

• Check the weight of the unit to determine a safe lifting method.
• Ensure that the lifting device is suitable for the task.
• If necessary, plan for a hoist, crane, or forklift with the appropriate rating to move the

unit.

• For lifting, use hoist rings on the unit, when provided.

Mounting

• Mount the unit vertically.
• The frequency converter allows side by side installation.
• Ensure that the strength of the mounting location will support the unit weight.
• Mount the unit to a solid flat surface or to the optional back plate to provide cooling

airflow.

Mechanical Installation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

51