Operation, Pre-start procedure, Pre-startup inspections – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 57: Pre-start procedure pre-startup inspections

Advertising
background image

Operation

Pre-start procedure

Electrical Hazard:
If input and output connections have been connected improperly, there is potential for
high voltage on these terminals. If power leads for multiple motors are improperly run in
same conduit, there is potential for leakage current to charge capacitors within the
frequency converter, even when disconnected from mains input. For initial start up, make
no assumptions about power components. Follow pre-start procedures. Failure to follow
pre-start procedures could result in personal injury or damage to equipment.

1. Make sure input power to unit is OFF and locked out. Do not rely on the frequency

converter disconnect switches for input power isolation.

2. Verify that there is no voltage on input terminals L1 (91), L2 (92), and L3 (93), phase-to-

phase and phase-to-ground.

3. Verify that there is no voltage on output terminals 96 (U), 97 (V), and 98 (W), phase-to-

phase and phase-to-ground.

4. Confirm continuity of the motor by measuring ohm values on U-V (96-97), V-W

(97-98), and W-U (98-96).

5. Check for proper grounding of the frequency converter as well as the motor.
6. Inspect the frequency converter for loose connections on terminals.
7. Record the following motor-nameplate data: power, voltage, frequency, full load

current, and nominal speed. These values are needed to program motor nameplate
data later.

8. Confirm that the supply voltage matches voltage of frequency converter and motor.

Pre-startup inspections

Item to Inspect

Description

Checked

Auxiliary equipment

• Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that may

reside on input power side of the frequency converter or output side to motor. Ensure they

are ready for full speed operation.

• Check function and installation of any sensors used for feedback to the frequency converter.
• Remove power factor correction caps on motor(s), if present.

Cable routing

• Ensure that input power, motor wiring and control wiring are separated or in three separate

metallic conduits for high frequency noise isolation.

Control wiring

• Check for broken or damaged wires and connections.
• Check that control wiring is isolated from power and motor wiring for noise immunity.
• Check the voltage source of the signals, if necessary.
• The use of shielded cable or twisted pair is recommended. Ensure that the shield is

terminated correctly.

Cooling clearance

• Measure that top and bottom clearance is adequate to ensure proper air flow for cooling.

EMC considerations

• Check for proper installation with regard to electromagnetic capability.

Environmental conditions

• See equipment tech label for the maximum ambient operation temperature limits.
• Humidity levels must be 5–95% non-condensing.

Fusing and circuit breakers

• Check for proper fusing or circuit breakers.
• Check that all fuses are inserted firmly and in operational condition and that all circuit

breakers are in the open position.

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

55