Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 131

Advertising
background image

Starting torque (variable torque)

maximum 110% for 60 s

1)

Overload torque (variable torque)

maximum 110% for 60 s

Torque rise time in VVC

plus

(independent of fsw)

10 ms

1)

Percentage relates to the nominal torque.

2)

The torque response time depends on application and load but as a general rule, the

torque step from 0 to reference is 4–5 x torque rise time.

Cable lengths and cross sections for control cables

1)

Maximum motor cable length, screened

150 m

Maximum motor cable length, unscreened

300 m

Maximum cross-section to control terminals, flexible/

rigid wire without cable end-sleeves

1.5 mm

2

/16 AWG

Maximum cross-section to control terminals, flexible wire

with cable end-sleeves

1 mm

2

/18 AWG

Maximum cross-section to control terminals, flexible wire

with cable end-sleeves with collar

0.5 mm

2

/20 AWG

Maximum cross section to control terminals

0.25 mm

2

/24 AWG

1)

For power cables, see Power Dependent Specifications.

Digital inputs

Programmable digital inputs

4 (6)

1)

Terminal number

18, 19, 27

1)

, 29

1)

, 32, 33

Logic

PNP or NPN

Voltage level

0–24 V DC

Voltage level, logic ‘0’ PNP

<5 V DC

Voltage level l, logic ‘1’ PNP

>10 V DC

Voltage level, logic ‘0’ NPN

2)

>19 V DC

Voltage level, logic ‘1’ NPN

2)

<14 V DC

Maximum voltage on input

28 V DC

Pulse frequency range

0–110 kHZ

(Duty cycle) Min. pulse width

4.5 ms

Input resistance, Ri

Approximately 4 kΩ

Analog inputs

Number of analog inputs

2

Terminal number

53, 54

Modes

Voltage or current

Mode select

Switch S201 and switch S202

Voltage mode

Switch S201/switch S202 = OFF (U)

Voltage level

—10 to +10 V (scaleable)

Input resistance Ri

Approximately 10 kΩ

Maximum voltage

±20 V

Current mode

Switch S201/switch S202 = ON (I)

Current level

0/4 to 20 mA (scaleable)

Input resistance Ri

Approximately 200Ω

Maximum current

30 mA

Technical Specification

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

129

Advertising