Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 51

Advertising
background image

Auto On

Pressing the [Auto On] key enables the drive to be

controlled via the control terminals and/or serial

communication. When a start signal is applied on the

control terminals and/or serial communication, the drive

will start. This key can be enabled or disabled via 0–42

[Auto On] key on LCP.

Reset

The [Reset] key is used for resetting the controller after an

alarm (trip). The key can be enabled or disabled via

parameter 0–43 [Reset] key on LCP.

Status lights

If certain threshold values are exceeded, the alarm and/or Warning (Warn.) LED will turn
on. If an alarm or warning is active, a status or alarm text will appear on the control panel.

• Yellow Warn. LED: Indicates a warning is active.
• Red Flashing Alarm LED: Indicates an alarm is active.

The On LED is activated when the controller receives power.

• Green On LED: Control section is powered and working.

Parameter backup

Parameter settings are stored internally in the controller. The parameters can be
uploaded to the LCP for backup or to easily transfer the parameter settings from one
controller to another controller. A factory reset does not change the data stored in the
LCP.
NOTE: Parameter data can be uploaded to the LCP through the use of the Start-Up Genie.
Simply select Copy to LCP from the setup selection menu at the beginning of the Genie.
To upload parameters to the LCP without the use of the Start-Up Genie follow the
following procedure:
1. Press [Off] to stop the motor before uploading data.
2. Press [Main Menu] to enter the parameter list.
3. Select 0-**Operation/Display, press [OK].
4. Use the down arrow to scroll to 0-5* Copy/Save, press [OK] to enter the submenu.
5. Press [OK] to enable editing of parameter 0-50 LCP Copy.
6. Use the up or down arrows to scroll to ALL to Copy, press [OK] to select.
7. The progress bar will show the status of the process.
8. Press [Status] to return to the main status screen.
9. Press [Auto On] or [Hand On] to resume previous operating mode.
NOTE: Parameter data can be uploaded to the LCP through use of the Start-Up Genie.
Simply select Copy from LCP from the setup selection menu at the beginning of the
Genie. Select All to copy all parameters from the LCP including size dependent data.
Select Application Only to copy all size independent data.
To download parameters to the controller from the LCP without use of the Start-Up Genie
follow the procedure below.

Electrical Installation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

49

Advertising