Parameter number

Parameter Name

Default Value

Parameter Description

20-21

Setpoint

50.0

Process setpoint. The

controller will adjust speed

to maintain this value. If

multiple setpoints are

enabled, this parameter will

display and allow

adjustment of the active

setpoint.

22-44

Restart Difference (%)

10%

This is the difference

between the setpoint and

feedback that will cause the

controller to restart from

sleep mode. This is entered

as a % of the setpoint. For a

50psi setpoint, a 10%

Restart Difference will cause

the controller to restart from

sleep at 45psi.

4–12

Sleep Frequency/Low

Limit[Hz]

30 Hz

This is the minimum speed

of the motor and the speed

at which the controller will

enter sleep mode.

5-11

Terminal 19 Digital Input

No operation

This general purpose digital

input is designated for the

Pump Protect Function.

5-12

Terminal 27 Digital Input

No operation

This general purpose digital

input is designated for the

Pump Protect Function.

22-00

Pump Protect Delay

10 s

This is the time delay

between detection of a

Pump Protect condition and

the triggering of the Pump

Protect Alarm.

22-26

No Water/Loss of Prime

Function

Man. Reset Alarm

This configures the No

Water/Loss of Prime

Function. Set this value to

Man. Reset Alarm in order

to utilize the No Water/Loss

of Prime Restart Function.

22-39

No Water/Loss of Prime

Limit

Size Dependent (HP)

This value sets the No

Water/Loss of Prime limit.

When the pump HP falls

below this value while

operating at maximum

speed, the No Water/Loss of

Prime Function will be

implemented after the time

specified in No Water/Loss

of Prime Protection Delay

[22-27].

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

59