Warning/Alarm

Description

Cause

Remedy

202 — Fire mode limits exceeded While operating in fire mode one

or more alarm conditions has been

ignored which would normally trip

the unit.

Operating in this condition voids

unit warranty.

Cycle power to the unit to remove

the warning. See the fire mode

data in the alarm log on the

controller.

203 — Missing motor

With a frequency converter

operating multi-motors, an under-

load condition was detected.

This could indicate a missing

motor.

Inspect the system for proper

operation.

204 — Locked rotor

With a frequency converter

operating multi-motors, an

overload condition was detected.

This could indicate a locked rotor. Inspect the motor for proper

operation.

250 — New spare part

A component in the frequency

converter has been replaced.

Reset the frequency converter for

normal operation.

251 — New typecode

A component in the frequency

converter has been replaced and

the typecode changed.

Reset the frequency converter for

normal operation.