Figure 33: Flow compensation when speed at design working point is unknown

Table 22: Flow compensation parameters when speed at design point is unknown

Parameter Number

Description

Set to

22–80

Flow Compensation

Enabled

22–81

Square-Linear Curve Approximation

Modify between 100% (square) and

0% (linear) per system requirements.

22–82

Work Point Calculation

Enabled — speed at design point is

unknown

22–84

Speed at No Flow [Hz]

To find this point, close all valves in

the system and run the pump at the

minimum head. The speed

corresponding to the minimum head

requirement at no flow will be

entered here. Point A.

22–87

Pressure at No Flow

System pressure at no flow and no

flow speed. This is the minimum

design head. Point A.

22–88

Pressure at Rated Speed

This setting corresponds to the head

developed at design flow and rated

speed. This value can be defined

using the pump performance curve.

Intersects with the design flow to

form point D.

22–89

Flow at Design Point

This setting corresponds to the

system design flow. Intersects with

the pressure at rated speed to form

point D and with the setpoint to form

point B.

22–90

Flow at Rated Speed

This setting corresponds to the flow at

rated speed. This value can be

defined using the pump performance

curve. Intersects with the setpoint to

form point C.

Dual pump value increase

In a Duplex Control System the friction losses can increase when both the lead and lag
pumps are running due to the additional flow in the system. When both pumps are
running, the Rated Curve and Design Curve shown above will change (reach higher flows
at a given pressure) when compared to when a single pump is running. This means that
the settings given to configure the Flow Compensation function may not be accurate
when both pumps are running. The Dual Pump Value Increase setting applies an increase
to the setpoint which will offset the additional losses associated with both pumps running.