details on installing shielded/screened cables. The parameter list in the table below
shows parameters used to configure communication for two common protocols, Modbus
RTU and BACnet. The parameter list in the second table below shows parameters that
determine the control source for certain drive functions. Use these parameters to
determine whether digital inputs or the BMS/PLC has control of the function.

Figure 27: Connections for external control source connected through comm. port

Table 10: Parameter settings for Modbus RTU and BACnet protocols

Parameter Number

Parameter Description

Protocol

Modbus RTU

BACnet

8-02

Control Source

FC Port

FC Port

8-30

Protocol

Modbus RTU

BACnet

8-31

Address

1

1

8-32

Baud Rate

19200

9600

8-33

Parity/Stop bit

Even Parity, 1 Stop bit

No Parity, 1 Stop bit

8-34

Estimated cycle time

0 ms

0 ms

8-35

Minimum Response Delay

10 ms

10 ms

8-36

Maximum Response Delay

5000 ms

5000 ms

8-37

Maximum Inter-Char Delay

0.86 ms

25 ms

Table 11: Parameters determining control source for controller functions

Parameter number

Description

Set to

8-01

Control Site

Determines the location of the control source.

Set to Digital and ctrl.word to use both serial

bus and digital input control. Set to Digital

only to use only the digital inputs. Set to

Controlword only to use only the serial bus.

8-50

Coasting Select

Determines the control location of the coasting

(stop) function. Set to Digital input to use a

digital input only. Set to Bus to use only the

serial bus only. Set to Logic AND to use the

serial bus AND a digital input. Set to Logic OR

to use the serial bus OR a digital input.

Electrical Installation