Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 68

Advertising
background image

Operating Mode

Description

Duplex Control

This mode configures the controller as part of a 2

controller, 2 pump system. Both pumps will run at the

same varying speed. The staging and destaging of

pumps can be configured to create a lead/lag system. The

lead pump can be alternated based on elapsed time.

Speed Control

This mode configures the controller to accept a speed

command through an analog input, pulse input or

extended PI loop [21–**]. A start signal on DI 18 [5–10] is

required.

Test Run Mode

Test Run Mode allows the controller to be configured to

run the pump at specified speed for a specified amount

of time. The action will be started by a digital input (DI

19).

Single pump

The Single Pump Operating Mode is the default operating mode for the controller. Use
this mode for constant pressure, flow or level applications that use 1 controller operating
a single pump.

• The Application Type allows selection of the type of control. Select either Constant

Pressure, Flow Control or Level Control.

• Next select the appropriate units for the application. These units will be displayed on

the LCP default status screen.

If Level Control is the Application Type, select whether the application is a Tank Fill or
Tank Empty application.

• In a ‘Fill’ application the pump will speed up when the level in the tank drops below

the setpoint level.

• In an ‘Empty’ application the pump will speed up when the level in the tank is above

setpoint level.

• The PID Normal/Inverse Control [20-81] parameter is set to Inverse for the ‘Empty’

application and to Normal for the ‘Fill’ application.

The ramp times are selected next. Select from either a Fast, Medium or Slow ramp.

Operation

66

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL