Relay and analog output setup – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 90

Advertising
background image

Digital I/O

Duplex Control Mode

Terminal Number

Parameter Number

Lead

Lag

Description

27

5–12

Setpoint increase

Pump Exercise Input When operating as

the lead pump, this

input will increase the

setpoint when both

pumps are on to

compensate for the

additional flow of the

lag pump. This

effectively performs a

flow compensation

function. When

operating as a lag

pump, this input acts

as the Pump Exercise

Input which will

perform the Pump

Exercise function. See

Duplex Control in the

Commissioning

section of this manual

for details.

29

5–13/5–31

I am Lead

I am Lead Inverse

Terminal 29 is

configured as an

output. This output is

used to indicate

which controller is the

lead pump and which

is the lag pump.

32

5–14

Slave Select

Slave Select

When this input is

high, the other

controller is operating

as the lead pump.

When high, this input

will force the

controller to become

the lag pump or enter

sleep mode if Duty

Standby is enabled.

33

5–15

[23] SP1/SP2 Select

[23] SP1/SP2 Select

Digital input.

Configured for use as

a Setpoint 1/Setpoint

2 select (SP1/SP2).

Open = SP1, Closed

= SP2.

20

Common

Common

supply

Relay and analog output setup

The Relay and Analog Output Setup allows configuration of the onboard relays and
analog output signal.

Operation

88

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL