Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 47

Advertising
background image

Freeze output

The remote reference is active, which holds the present

speed.

• Freeze output was selected as a function for a digital

input (parameter group 5–1* Digital Inputs). The

corresponding terminal is active. Speed control is

only possible via the terminal functions Speed Up

and Speed Down.

• Hold ramp is activated via serial communication.

Freeze output request

A freeze output command has been given, but the motor

will remain stopped until a run permissive signal is

received.

Freeze Reference

Freeze Reference was chosen as a function for a digital

input (parameter group 5–1* Digital Inputs). This

corresponding terminal is active. The controller saves the

actual reference. Changing the reference is now only

possible via terminal functions Speed Up and Speed

Down.

Jog request

A jog command has been given, but the motor will be

stopped until a run permissive signal is received via a

digital input.

Jogging

The motor is running as programmed in 3–19 Jog Speed

[RPM].

• Jog was selected as function for a digital input

(parameter group 5–1* Digital Inputs). The

corresponding terminal (e.g. Terminal 29) is active.

• The Jog Function is activated via the serial

communication.

• The Jog function was selected as a reaction for a

monitoring function (e.g. No signal). The

monitoring function is active.

Motor check

In 1–80 Function at Stop, Motor Check was selected. A

stop command is active. To ensure that a motor is

connected to the controller, a permanent test current is

applied to the motor.

OVC control

Overvoltage control was activated in 2–17 Overvoltage

Control, [2] Enabled. The connected motor is supplying

the controller with generative energy. The overvoltage

control adjusts the V/Hz ratio to run the motor in

controlled mode and to prevent the controller from

tripping.

PowerUnit Off

(For controllers with an external 24 V power supply

installed only.) Mains supply to the controller is removed,

but the control card is supplied by the external 24 V.

Protection md

Protection mode is active. The unit has detected a critical

status (an overcurrent or overvoltage).

• To avoid tripping, switching frequency is reduced to

4 kHz.

• If possible, protection mode ends after

approximately 10 s

• Protection mode can be restricted in 14–26 Trip

Delay at Inverter Fault

Electrical Installation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

45