Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 117

Advertising
background image

Warning/Alarm

Description

Cause

Remedy

38 — Internal fault

When an internal fault occurs, a

code number defined in the table

below is displayed.

Cycle power to the frequency

converter.
Check that the option is properly

installed.
Check for loose or missing wiring.
It may be necessary to contact your

Xylem supplier or service

department. Note the code

number for further

troubleshooting directions.

39 — Heatsink sensor

No feedback from the heatsink

temperature sensor.

The signal from the IGBT Thermal

sensor is not available on the

power card. The problem could be

on the power card, on the gate

drive card, or the ribbon cable

between the power card and gate

drive card.

40 — Overload of digital output

terminal 27

Check the load connected to

terminal 27 or remove short-circuit

connection.
Check [5–00] Digital I/O Mode and

5–01 Terminal 27 Mode.

41 — Overload of digital output

terminal 29

Check the load connected to

terminal 29 or remove short-circuit

connection.
Check [5–00] Digital I/O Mode and

[5–02] Terminal 29 Mode.

42 — Overload of digital output on

X30/6 or overload of digital output

on X30/7

For X30/6, check the load

connected to X30/6 or remove

short-circuit connection. Check 5–

32 Term X30/6 Digi Out (General

Purpose I/O Option Card).
For X30/7, check the load

connected to X30/7 or remove

short-circuit connection. Check 5–

33 Term X30/7 Digi Out (General

Purpose I/O Option Card).

45 — Ground fault 2

Ground (earth) fault on startup.

Check for proper grounding

(earthing) and loose connections.
Check for proper wire size.
Check motor cables for short-

circuits or leakage currents.

46 — Power card supply

The supply on the power card is

out of range.

There are three power supplies

generated by the switch mode

power supply (SMPS) on the

power card: 24 V, 5 V, +/- 18 V.

When powered with 24 VDC with

the 24VDC Backup Option Card

option, only the 24 V and 5 V

supplies are monitored. When

powered with three-phase mains

voltage, all three supplied are

monitored.

Check for a defective power cord.
Check for a defective control card.
Check for a defective option card.
If a 24 VDC power supply is used,

verify proper supply power.

47 — 24 V supply low

The 24 V DC is measured on the

control card.

The external 24 V DC backup

power supply may be overloaded.

Contact your Xylem supplier.

Warnings and alarms