Setup and commissioning

Start-Up Genie

CAUTION:
When a Start (Closed) signal is present on DI18, the controller can start the pump/motor
at any time without warning. Set DI18 to Stop (Open) or press the [Off] operation key
before using the Genie. Apply the Start signal to the controller only when pump/motor
operation is desired.

The Start-Up Genie provides a fast and easy method for configuring the controller for
various pump applications. The Navigation keys are used to make selections within the
Genie. The [Info] button can be pressed at any time while in the Genie to retrieve
additional information about the current screen or parameter.
To navigate through the Start-Up Genie, press [OK] to enable editing of a screen or
parameter. Use the up and down arrows to highlight the desired selection then press [OK]
to confirm the selection. Next use the down arrow to save the parameter and navigate to
the next screen. The up arrow transitions to the previous screen. If the screen shows the
desired setting is already selected for a particular parameter or function, simply use the
down arrow to proceed to the next screen.
NOTE: Be sure to press the down arrow to save the parameter after confirming the
selection. This ensures all associated parameter settings and background calculations are
performed and saved properly. After pressing the down arrow to save the parameter the
Genie may be slow to respond as these settings and calculations are performed.
Press [Cancel] to exit parameter editing without saving or to change a saved parameter or
selection back to the previously saved while still in the current screen. Pressing [Back] will
also exit parameter editing without saving. To exit the Start-Up Genie at any time, first exit
parameter editing then press [Back] then [OK].
The arrows shown in the lower right hand corner of the LCP indicate the options for
navigation. When an up arrow is displayed, pressing the up arrow will transition to the
previous screen. When a down arrow is displayed, pressing the down arrow will transition
to the next screen. When both an up and down arrow are displayed then pressing the up
arrow will transition to the previous screen and pressing the down arrow will transition to
the next screen.
NOTE: Ensure the controller is set to Stop (DI 18 Open) and is set to Setup 1 prior to
running the Start-Up Genie. To place the controller in Setup 1, ensure DI 33 is Open and
the controller is set to Lead for Duplex systems. To manually change the lead pump in a
Duplex System press [OK] and the right arrow keys on the lead drive. In Duplex Systems
ensure alternation does not occur while running the Start-Up Genie by pressing [Off]
before entering the Start-Up Genie.
The Genie starts automatically the first time the controller has been powered in the field
or if the Genie has not been used previously. The Genie can be started at any time by
accessing the Quick Menus screen by pressing [Quick Menu] then using the up and down
arrows to highlight Q4 Start-Up Genie. Press [OK] to enter the Genie.