Warning/Alarm

Description

Cause

Remedy

48 — 1.8 V supply low

The power supply is measured on

the control card.

The 1.8 V DC supply used on the

control card is outside of allowable

limits.

Check for a defective control card.
If an option card is present, check

for an overvoltage condition.

49 — Speed limit

When the speed is not within the

specified range in [4–11] Motor

Speed Low Limit [RPM] and [4–13]

Motor Speed High Limit [RPM],

the frequency converter will show

a warning.

When the speed is below the

specified limit in [1–86] Trip

Speed Low [RPM] (except when

starting or stopping) the frequency

converter will trip.

50 — AMA calibration failed

Contact your Xylem supplier or

Xylem Service Department.

51 — AMA check Unom and Inom The settings for motor voltage,

motor current, and motor power

are wrong.

Check the settings in parameters

1–20 to 1–25.

52 — AMA low Inom

The motor current is too low.

Check the setting in [4–18]

Current Limit.

53 — AMA motor too big

The motor is too big for the AMA to

operate.

54 — AMA motor too small

The motor is too small for the AMA

to operate.

55 — AMA Parameter out of range The parameter values of the motor

are outside of the acceptable

range. AMA will not run.

56 — AMA interrupted by the user The AMA has been interrupted by

the user.

57 — AMA timeout

Try to restart AMA again. Repeated

restarts may overheat the motor.

58 — AMA internal fault

Contact your Xylem supplier.

59 — Current limit

The current is higher than the

value in [4–18] Current Limit.

Ensure that motor data in

parameters 1–20 through 1–25

are set correctly.
Possibly increase the current limit.

Be sure that the system can

operate safely at a higher limit.

60 — Pump Protect

A digital input signal is indicating

a pump protection external to the

controller is active.

62 — Output frequency at

maximum limit

The output frequency has reached

the value set in [4–19] Max Output

Frequency.

Check the application to

determine the cause. Possibly

increase the output frequency. Be

sure the system can operate safely

at a higher output frequency. The

warning will clear wieh the output

drops below the maximum limit.

65 — Control card over

temperature

The cut-out temperature of the

control card is 80°C.

Check that the ambient operating

temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the control card.

Warnings and alarms

116

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL