Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual
Page 40

switches based on the type of output signal. The diagrams below show the connections
for an external speed command.
• Speed control mode can be configured using the Start-Up Genie.
Figure 23: Connections for speed control with external potentiometer
Figure 24: Connections for speed control with PLC or BMS
Table 8: Parameters for speed control from external potentiometer, PLC or BMS
Parameter number
Description
Set to
1-00
Configuration Mode
Open Loop
3-15
Reference 1 Source
Analog Input 53
3-02
Minimum Reference
Set to value corresponding to desired
speed at the minimum reference
3-03
Maximum Reference
Set to value corresponding to desired
speed at the maximum reference
3-15
Reference 1 Source
Analog Input 53***
6-10*
Terminal 53 Low Voltage*
0 V
6-11*
Terminal 53 High Voltage*
10 V
6-12**
Terminal 53 Low Current**
4 mA
6-13**
Terminal 53 High Current**
20 mA
6-14
Terminal 53 Low Ref./Feedb. Value
Set to value corresponding to the
commanded speed at the low
voltage/current.
6-15
Terminal 53 High Ref./Feedb. Value
Set to value corresponding to the
commanded speed at the high
voltage/current.
6-17
Terminal 53 Sensor Fault
Disabled
2000
Feedback 1 Source
No Function
Electrical Installation
38
Aquavar
®
Intelligent Pump Controller INSTRUCTION MANUAL