• A Fast ramp setting will have a 5 second acceleration ramp time and an 8 second

deceleration time.

• A Medium ramp setting will have a 10 second acceleration ramp time and a 10

second deceleration time.

• A Slow ramp setting will have a 20 second acceleration ramp time and a 15 second

deceleration time.

• Acceleration ramps are set in Parameters [3-41] and [3-51]. Deceleration ramps are

set in Parameters [3-42] and [3-52].

The next screen will allow the user to automatically configure the rest of the parameters to
default settings. The only parameter that must be set after selecting [Yes] is the setpoint.
After the setpoint is configured the setup of the controller is complete. The default
configurations are described in the table below. Note that [unit] will reflect the control
units selected previously. If No is selected the Genie will prompt to proceed to the
Feedback Setup.

Table 19: Autoset configuration

Autoset Configuration

Constant Pressure

Level Control

Flow Control

Transducer Max Feedback

300 [unit]

300 [unit]

300 [unit]

Transducer Type

4-20mA

4-20mA

4-20mA

Feedback 1 Source

AI 53

AI 53

AI 53

PID Performance

Normal

Fill (Normal)

Normal

Sleep Mode

Enabled

Enabled

Disabled

Sleep Frequency

30 Hz

30 Hz

NA

Restart Difference

5 [unit]

5 [unit]

NA

No Water/Loss of Prime

Fault

Enabled

Enabled

Enabled

No Water/Loss of Prime

Restart Time

10 min.

10 min.

10 min.

Constant slave

The Constant Slave Operating Mode allows control of up to 2 external fixed speed pumps
using the 2 on board relays. This mode can be used to extend the capacity of a system by
staging fixed speed pumps as the demand in the system increases. Pumps can then be
destaged as the system demand decreases. The variable speed pump is always the lead
pump. The fixed speed pumps can be staged and destaged to create a lead/lag system.

The Application Type can be set to either Constant Pressure or Level Control. Set control
variable units and ramps as described in Single Pump Operating Mode.

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL