Basic operational programming – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 96

Advertising
background image

the up and down arrows to select parameter 0-70 Date and Time. Press [OK] to enabling
editing of the Date and Time parameter. First set the time. Use the up and down arrows to
set the minutes. Then use the left arrow key to scroll left to the hours. Use the up and
down arrows to set the hour of the day. To change to PM, press the up arrow key until the
desired hours and the letter P (found between the minutes and day of the week) are
shown on the display. Next, scroll to the left to set the date. The day of the week on the
right side will update according to the date selected. Press [OK] to save the changes.
NOTE: If the power to the unit is lost, the date and time will reset to factory defaults.
Battery backup for real time clock is available on the Analog I/O Option Card (Input/
Output Option "A" or Repair part number 9K653).

Basic operational programming

Required initial frequency converter programming

NOTE: If the Start-Up Genie is run, ignore the following.
Frequency converters require basic operational programming before running for best
performance. Basic operational programming requires entering motor-nameplate data
for the motor being operated and the minimum and maximum motor speeds. Enter data
in accordance with the following procedure. Parameter settings recommended are
intended for start up and checkout purposes. Application settings may vary. See the Local
Control Panel section for detailed instructions on entering data through the LCP.
Enter data with power ON, but before operating the frequency converter.
1. Press [Main Menu] twice on the LCP.
2. Use the navigation keys to scroll to parameter group 0–** Operation/Display and

press [OK].

Figure 34: Main menu

3. Use navigation keys to scroll to parameter group 0–0* Basic settings and press [OK].

Figure 35: Operation/display

4. Use navigation keys to scroll to 0–3 Regional Settings and press [OK].

Figure 36: Basic settings

Operation

94

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL