Warnings and alarms – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 112

Advertising
background image

Number

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

70

Illegal FC

configuration

X

71

PTC 1 Safe Stop

X

X

1)

72

Dangerous failure

X

1)

73

Safe Stop Auto Restart

76

Power Unit Setup

X

77

Reduced Power Mode

79

Illegal PS config

X

X

80

Drive initialized to

Default value

X

91

Analog input 54

wrong settings

X

92

No Flow

X

X

22–2*

93

No Water/Loss of

Prime

X

X

22–2*

94

Under Pressure

X

X

22–5*

95

Broken Belt

X

X

22–6*

96

Start Delayed

X

22–7*

97

Start Delayed

X

22–7*

201

Fire M was Active

202

Fire M Limits

Exceeded

203

Missing Motor

204

Locked Rotor

243

Brake IGBT

X

X

244

Heatsink temp

X

X

X

245

Heatsink sensor

X

X

246

Pwr. card supply

X

X

247

Pwr.card Temp

X

X

248

Illegal PS config

X

X

250

New spare parts

X

251

New Type Code

X

X

(X) Dependent on parameter
1) Cannot be Auto reset via 14–20 Reset Mode

Warnings and alarms

Warning/Alarm

Description

Cause

Remedy

1 — 10 V low

The control card voltage is below

10 V from terminal 50.

A short in a connected

potentiometer or improper wiring

of the potentiometer.

Remove the wiring from terminal

50. If the warning clears, the

problem is with the customer

wiring.

Warnings and alarms

110

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL