Warning/Alarm

Description

Cause

Remedy

26 — Brake resistor power limit

The power transmitted to the

brake resistor is calculated as a

mean value over the last 120

seconds of run time. The

calculation is based on the

intermediate circuit voltage and

the brake resistance value set in

[2–16] brake Max. Current.

The warning is active when the

dissipated braking is higher than

90% of the brake resistance

power.
If Trip [2] is selected in [2–13]

Brake Power Monitoring, the

frequency converter will trip when

the dissipated braking power

reaches 100%.

27 — Brake chopper fault

The brake transistor is monitored

during operation and if a short

circuit occurs, the brake function is

disabled and a warning is issued.

The frequency converter is still

operational but, since the brake

transistor has short-circuited,

substantial power is transmitted to

the brake resistor, even if it is

inactive.

Remove power to the frequency

converter and remove the brake

resistor.

28 — Brake check failed

The brake resistor is not connected

or not working.

Check [2–15] Brake Check.

29 — Heatsink temp

The maximum temperature of the

heatsink has been exceeded. The

temperature fault will not reset

until the temperature falls below

the reset heatsink temperature.

The trip and reset points are based

on the frequency converter power

size.

Check for the following conditions:

• Ambient temperature too

high.

• Motor cable too long.
• Incorrect airflow clearance

above and below the

frequency converter.

• Blocked airflow around the

frequency converter.

• Damaged heatsink fan.
• Dirty heatsink.

30 — Motor phase U missing

Motor phase U between the

frequency converter and the motor

is missing.

Remove power from the frequency

converter and check motor phase

U.

31 — Motor phase V missing

Motor phase V between the

frequency converter and the motor

is missing.

Remove power from the frequency

converter and check motor phase

V.

32 — Motor phase W missing

Motor phase W between the

frequency converter and the motor

is missing.

Remove power from the frequency

converter and check motor phase

W.

33 — Inrush fault

Too many power-ups have

occurred within a short time

period.

Let the unit cool to operating

temperature.

34 — Fieldbus communication

fault

Communication between the

fieldbus and the communication

option card is not operating.

36 — Mains failure

This warning/alarm is only active if

the supply voltage to the

frequency converter is lost and 14–

10 Mains Failure is NOT set to [0]

No Function.

Check the fuses to the frequency

converter and mains power supply

to the unit.

Warnings and alarms