Wiring to control terminals, Unplug terminal connectors, Control terminal connections – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 31

Advertising
background image

Terminal number

Parameter number

Default setting or

function

Description

Analog I/O

39

AO Common

Common for analog

output

42

6–50

[137] Speed 420 mA Analog output.

Default setting is

4-20mA signal (500Ω

max) based on motor

speed. Range is 0 to

max speed indicated

in parameter 4-14.

50

+10V DC

10V DC analog supply

voltage. 15mA

maximum.

53

6–1*

Transducer feedback Analog input 53.

Default configuration

is 300 psi, 4-20mA

pressure transducer

input.

54

6–2*

Not Used

Analog input 54

55

AI Common

Common for analog

input

Comm.

61

Shield Connection

Integrated RC filter for

cable shield. ONLY for

connecting the shield

when experiencing

EMC problems.

68

8–3*

+

RS485 interface +

69

8–3*

RS485 interface –

Wiring to control terminals

Unplug terminal connectors

Control terminal connectors can be unplugged from the frequency converter for ease of
installation.

Control terminal connections

Connecting to the control terminals

1. To connect control wiring to the control terminals, do the following:

a. Strip the control wire back 9–10mm (0.35–0.40 in)
b. Insert a screwdriver (0.4 x 2.5 mm) in the rectangular hole.

Electrical Installation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

29