The analog output (AO 42, parameter 6–50) can be configured to output various
controller parameters. This output is a current output (0–20mA or 4–20mA). Refer to the
Common Terminal Wiring section in this manual for details on wiring. The list of analog
output configuration options is shown below.

Option

Function

[0]*

No operation

[100]

Output freq. 0–100

0–100 Hz, (0–20 mA)

[101]

Reference Min-Max

Minimum reference — Maximum

Reference, (0–20 mA)

[102]

Feedback +–200%

–200% to +200% of [20–14]

Maximum Reference/Feedb., (0–20

mA)

[104]

Torque 0–Tlim

0–Torque limit ([4–16] Torque Limit

Motor Mode), (0–20 mA)

[105]

Torque 0–Tnom

0–Motor rated torque, (0–20 mA)

[106]

Power 0–Pnom

0–Motor rated power, (0–20 mA)

[107]*

Speed 0–HighLim

0–Speed High Limit ([4–13] Motor

Speed Limit [RPM] and [4–14] Motor

Speed High Limit [Hz]), (0–20 mA)

[113]

Ext. Closed Loop 1

0–100%, (0–20 mA)

[114]

Ext. Closed Loop 2

0–100%, (0–20 mA)

[115]

Ext. Closed Loop 3

0–100%, (0–20 mA)

[130]

Out frq 0–100 4–20mA

0–100 Hz

[131]

Reference 4–20mA

Minimum Reference — Maximum

Reference

[132]

Feedback 4–20mA

–200% to +200% of [20–14]

Maximum Reference/Feedb.

[133]

Motor cur. 4–20 mA

0–Inverter Max. Current ([16–37] Inv.

Max. Current)