Digital I/O

Operating Mode

Terminal Number Parameter

Number

Single Pump/

Constant Slave

Speed Control

Test Run Mode

Description

32

5–14

[1] Restart

[0] No Operation [0] No Operation Configured for

use as a Reset for

the No Water/Loss

of Prime Restart

function for

Single Pump and

Constant Slave

modes. Refer to

the Pump

Protection section

for details.

33

5–15

[23] SP1/SP2

Select

[23] SP1/SP2

Select

[23] SP1/SP2

Select

Digital input.

Configured for

use as a Setpoint

1/Setpoint 2

select (SP1/SP2)

20

Common

Common

Common

Common for

digital inputs and

reference for 24 V

supply

Table 24: Digital input functionality based for duplex mode

Digital I/O

Duplex Control Mode

Terminal Number

Parameter Number

Lead

Lag

Description

18

5–10

[8] Start

[8] Start

Start/Stop digital

input signal for the

drive. Connect input

to 24 V to start. Open

the input to stop. This

is a required

connection.

19

5–11

[0] No Operation

[0] No Operation

Unused digital input.

This input can be

configured for use as

a Pump Protect

Warning or Alarm

input. See Pump

Protect section to

enable the Warning

or Alarm associated

with this input.