Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 73

Advertising
background image

NOTE: If Pump Exercise is enabled, the pump will run after alternation of the lead pump
even if there is no demand in the system.
NOTE: If Duty Standby is enabled, Pump Exercise cannot be disabled. Refer to the table
below for details.
The settings for Duty Standby, Pump Exercise and Start Delay can impact when a pump is
expected to start. The table below shows how these settings impact when a pump will
start.

Duty Standby

Pump Exercise

Explanation

Disabled

Disabled

If both controls are given a start command at the same

time or both controls are reset from a fault at the same

time, both pumps will run until the lead pump and lag

pump roles are established. With both functions

disabled, the duplex system will operate as a lead/lag

system. On Alternation, the new lead pump will not run

unless there is demand in the system.

Disabled

Enabled

The lag pump will start when the lead pump wakes up

from sleep or if the lead pump is stopped and is then

given a start command. For these conditions the lag

pump will run for the time specified in Pump Exercise

Time [22-40]. The lag will continue to run if the speed

command from the lead pump is greater than the Lag

Pump Stop Frequency [4-12].
On Alternation, the new lead pump will run for the time

specified in Pump Exercise Time. After the Pump Exercise

Time, the pump will continue to run if demand is present

or will go to sleep if there is no demand.

Enabled

Enabled

On Alternation and no demand, the new lead pump will

start and run for the time specified by Pump Exercise

Time [22-40] or Sleep Delay [22-24], whichever is longer.

The pump will then go to sleep, if enabled.
On Alternation with demand, the new lead pump will

ramp up while the previous lead pump is ramping down.

In order to ensure both pumps do not run at the same

time in this condition, set the Start Delay [1-71] time

longer than the Ramp Down Time [3-42].

Start delay

The Start Delay Function delays the lead pump from starting for the time specified. This
function can be used to prevent rapid cycling of the system or to prevent the new lead
pump from starting up while the lag pump is ramping down during alternation. For
example, if the Start Delay Time is set to 10 seconds and the pump is given a start
command, the pump will start 10 seconds after the command to start is received by the
controller. In a Duplex System with the Start Delay set to 10 seconds, if Alternation is
enabled and the Alternation Time expires the new lead pump will start after a 10 second
delay. If Duty Standby is enabled, set the Start Delay longer than the Ramp Down Time
[3-42]
of the other pump to ensure both pumps do not run at the same time.

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

71

Advertising