1. Press [Off] to stop the motor before uploading data.
2. Press [Main Menu] to enter the parameter list.
3. Select 0-** Operation/Display, press [OK].
4. Use the down arrow to scroll to 0-5* Copy/Save, press [OK] to enter the submenu.
5. Press [OK] to enable editing of parameter 0-50 LCP Copy.
6. To copy all data from the LCP, including size dependent data, use the up or down

arrows to scroll to All from LCP, press [OK] to select. To copy all size independent
data, scroll to Size indep. from LCP, press [OK] to select.

7. The progress bar will show the status of the process.
8. Press [Status] to return to the main status screen.
9. Press [Auto On] or [Hand On] to resume previous operating mode.

Factory Reset

A factory reset can be performed to restore the controller back to default settings. There
are multiple ways to perform this function.
Parameter 14-22 Operation Mode can be used to perform the factory reset function.
Using this method does not change controller data such as operating hours, serial
communication selections, fault log, alarm log, and other monitoring functions. To
perform the reset through parameter 14-22 perform the following steps.
1. Press [Main Menu] to enter the parameter list.
2. Use the up and down arrows to scroll to 14-** Special Functions, press [OK].
3. Use the up and down arrows to scroll to 14-2* Reset Functions, press [OK].
4. Use the up and down arrows to scroll to 14-22 Operation Mode, press [OK].
5. Press [OK] to enable modification of the parameter.
6. Use the up and down arrows to scroll to Initialization, press [OK].
7. Remove input power from the unit and wait for the LCP to turn off.
8. Apply power to the unit. The reset is performed at power up.
9. Alarm 80 Drive Initialized to Default Value will be displayed.
10. Press [Reset] to return to operation mode.
Another way to perform the factory reset is to issue a 3 finger reset. The process is
described below.
1. Remove power from the unit and wait for the LCP to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at the same time. While holding down

the buttons, apply power to the unit.