Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 129

Advertising
background image

Table 39: Mains supply 3 x 525–600 V AC Normal overload 110% for 1 minute, 20HP - 125HP

Frequency type designation

0200 0250 0300 0400 0500 0600 0750 1000 1250

Typical shaft output [HP]

20

25

30

40

50

60

75

100

125

IP20/Chassis

B3

B3

B4

B4

B4

C3

C3

C4

C4

IP21/NEMA 1

B1

B1

B2

B2

C1

C1

C1

C2

C2

IP55/Type 12

B1

B1

B2

B2

C1

C1

C1

C2

C2

IP66/NEMA 4X

B1

B1

B2

B2

C1

C1

C1

C2

C2

Output current
Continuous (3 x 525–550 V) [A]

23

28

36

43

54

65

87

105

137

Intermittent (3 x 525–550 V) [A]

25

31

40

47

59

72

96

116

151

Continuous (3 x 525–600 V) [A]

22

27

34

41

52

62

83

100

131

Intermittent (3 x 525–600 V) [A]

24

30

37

45

57

68

91

110

144

Continuous kVA (525 V AC) [kVa]

21.9 26.7 34.3

41

51.4 61.9 82.9

100 130.5

Continuous kVA (575 V AC) [kVA]

21.9 26.9 33.9 40.8 51.8 61.7 82.7 99.6 130.5

Maximum input current
Continuous (3 x 525–600 V) [A]

20.9 25.4 32.7

39

49

59

78.9 95.3 124.3

Intermittent (3 x 525–600 V) [A]

23

28

36

43

54

65

87

105

137

Additional specifications
Estimated power loss at rated maximum load [W]

4)

400

475

525

700

750

850 1100 1400 1500

IP20 maximum cable cross-section (mains, motor, brake, and load

sharing) [mm

2

]/[AWG]

10,

10, -

(8, 8,

-)

35, -, - (2, -, -)

50,-,- (1,-,-)

150 (300 MCM)

IP55, IP66 maximum cable cross-section (mains, motor, brake, and

load sharing) [mm

2

]/[AWG]

16,

10, 10

(6, 8,

8)

35,-,-(2,-,-)

50,-,- (1,-,-)

95 (4/0)

Maximum cable cross-section with disconnect

16, 10, 10 (6, 8, 8)

50, 35, 35 (1, 2, 2)

95,

70, 70

(3/0,

2/0,

2/0)

185, 150, 120

(350 MCM,

300 MCM,

4/0)

Mains disconnect switch included:

16/6

35/2

70/3/

0

185/

kcmil

350

Weight IP20 [kg]

12

12

23.5 23.5 23.5

35

35

50

50

Wright IP21/55 [kg]

23

23

27

27

27

45

45

65

65

Efficiency

4)

0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98

2) For type of fuse, see Fuse Specifications
3) American Wire Gauge
4) Measured using 5 m screened motor cables at rated load and rated frequency
5) The typical power loss at normal load conditions and expected to be within ±15%
(tolerance relates to variety in voltage and cable conditions).

• Values are based on a typical motor efficiency (eff2/eff3 border line). Lower efficiency

motor will also add to the power loss in the frequency converter and vice versa.

• If the switch frequency is raised from nominal the power losses may rise significantly.

Technical Specification

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

127