Table 23: Digital input functionality based on operating mode

Digital I/O

Operating Mode

Terminal Number Parameter

Number

Single Pump/

Constant Slave

Speed Control

Test Run Mode

Description

18

5–10

[8] Start

[8] Start

[14] Jog

Start/Stop digital

input signal for

the drive. Connect

input to 24 V to

start. Open the

input to stop. This

is a required

connection. In

Test Run Mode,

this input starts

the test run.

19

5–11

[0] No Operation [0] No Operation [0] No Operation Unused digital

input. This input

can be configured

for use as a Pump

Protect Warning

or Alarm Input.

See Pump Protect

section to enable

the Warning or

Alarm associated

with the input.

27

5–12

[0] No Operation [0] No Operation [0] No Operation Unused digital

input for all

models. This

input can be

configured for use

as a Pump Protect

Warning or Alarm

input. See Pump

Protect section to

enable the

Warning or Alarm

associated with

this input.

29

5–13/5–31

[63] No Water/

Loss of Prime

Restart (CMP3)

[0] No Operation [0] No Operation Selectable for

digital input or

output. Default

configuration is

an output that is

configured for use

as a No Water/

Loss of Prime

Restart signal in

the Single Pump

and Constant

Slave mode. Refer

to the Pump

Protection section

for details.

Operation

86

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL