Warning/Alarm

Description

Cause

Remedy

66 — Heatsink temperature low

The frequency converter is too cold

to operate. This warning is based

on the temperature sensor in the

IGBT module.

Increase the ambient temperature

of the unit.
A trickle amount of current can be

supplied to the frequency

controller whenever the motor is

stopped by setting [2–00] DC

Hold/Preheat Current at 5% and

[1–80] Function at Stop.

67 — Option module configuration

has changed

One or more options have either

been added or removed since the

last power down.

Check that the configuration

change is intentional and reset the

frequency controller.

68 — Safe stop activated

Loss of the 24 VDC signal on

terminal 37 has caused the

frequency controller to trip.

To resume normal operation,

apply 24 VDC to terminal 37 and

reset the frequency controller.

69 — Power card temperature

The temperature sensor on the

power card is either too hot or too

cold.

Check that the ambient operating

temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.

70 — Illegal FC configuration

The control card and power card

are incompatible.

Contact your supplier with the

typecode of the unit from the

80 — Drive initialized to default

value

Parameter settings are initialized

to default settings after a manual

reset.

Reset the unit to clear the alarm.

92 — No flow

A no-flow condition has been

detected in the system.

[22–23] No-Flow Function is set for

alarm.

Troubleshoot the system and reset

the frequency converter after the

fault has been cleared.

93 — No Water/Loss of Prime

A low power condition in the

system with the frequency

converter operating at high speed

may indicate a the pump is out of

water or has lost prime.

[22–26] No Water/Loss of Prime

Function is set for alarm. The [22–

39] No Water/Loss of Prime Limit

is set too high.

Troubleshoot the system and reset

the frequency converter after the

fault has been cleared.

94 — Under Pressure

The system pressure is below the

Under Pressure limit (Under

Pressure Limit = Setpoint [22–25]

Under Pressure Difference).

This may indicate leakage in the

system. [22–50] Under Pressure

Function is set for alarm.

Troubleshoot the system, and

reset the frequency converter after

the fault has been cleared.

95 — Broken belt

Torque is below the torque level

set for no load, indicating a broken

belt.

[22–60] Broken Belt Function is

set for alarm.

Troubleshoot the system and reset

the frequency converter after the

fault has been cleared.

96 — Start delayed

Motor start has been delayed due

to short-cycle protection.

[22–76] Interval between Starts is

enabled.

Troubleshoot the system and reset

the frequency converter after the

fault has been cleared.

97 — Stop delayed

Stopping the motor has been

delayed due to short cycle

protection.

[22–76] Interval between Starts us

enabled.

Troubleshoot the system and reset

the frequency converter after the

fault has been cleared.

98 — Clock fault

Time is not set or the RTC clock has

failed.

Reset the clock in [0–70] Date and

Time.

200 — Fire mode

This indicates the frequency

controller is operating in fire

mode.

Cycle power to the unit to remove

the warning. See the fire mode

data in the alarm log on the

controller.

201 — Fire mode was active

This indicates the frequency

controller had entered fire mode.

Cycle power to the unit to remove

the warning. See the fire mode

data in the alarm log on the

controller.

Warnings and alarms