Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 37

Advertising
background image

Protect Alarm to prevent nuisance tripping. When the input is disconnected from the 24V
supply, the delay timer will start. If the input remains disconnected for the time indicated
in [22-00] Pump Protect Delay, the controller stops the motor and issues Alarm 60 Pump
Protect
. If a Pump Protect Alarm is issued, the controller will attempt to restart if the
[14-20] Reset Mode parameter and the [14-21] Automatic Restart Time parameter are set
to allow automatic restarting. To prevent an automatic restart set the [14-20] Reset Mode
to Manual Reset. Note that the [14-20] Reset Mode parameter affects all other Alarms that
are not listed as a Trip Lock Alarm. Refer to the Warnings/Alarm Messages section for
details.
NOTE: This function can be enabled using the Start-Up Genie.

Figure 20: Connections for adding Pump Protect

Table 5: Parameter settings for enabling a Pump Protect Alarm on DI19

Parameter number

Parameter description

Set to

5–11*

Terminal 19 Digital Input

Pump Protect

22–00

Pump Protect Delay

Set to the desired delay time. If set to

10 seconds, the Pump Protect Alarm

will be issued 10 seconds after the

input is disconnected from 24V. The

input must remain disconnected for

the entire delay time for the alarm to

be issued.

14–20

Reset Mode

Set to the desired number of

automatic resets. If a fault occurs

more than this setting, a manual

reset is required. Set to Manual Reset

if no resets are allowed. Default

setting is: Automatic reset x 3.

14–21

Automatic Restart Time

This is the time between when an

alarm/warning is issued and when

the controller attempts the next

restart. Default setting is 30 seconds.

* To configure DI 27, set 5–12 to Pump Protect.

Configuring an additional transducer feedback

An additional transducer can be added to the system to work with closed loop control or
for external monitoring. The additional transducer can be either a voltage output or
current output transducer. The additional transducer can be added to the unused analog
input (AI 53 or AI 54). The wiring below shows the required connections for an additional
transducer on AI 54.

Electrical Installation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

35