Item to Inspect

Description

Checked

Grounding (earthing)

• The unit requires an earth wire (ground wire) from its chassis to the building ground

(earth) .

• Check for good earth connections (ground connections) that are tight and free of oxidation.
• grounding (earthing) to conduit or mounting the back panel to a metal surface is not a

suitable ground (earth) .

Input and output power

wiring

• Check for loose connections.
• Check that motor and mains are in separate conduit or separated screened cables.

Panel interior

• Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.

Switches

• Ensure that all switch and disconnect settings are in the proper positions.

Vibration

• Check that the unit is mounted solidly or that shock mounts are used, as necessary.
• Check for an unusual amount of vibration.

Checked by:
Date:

Apply power

NOTICE:

• HIGH VOLTAGE. Frequency converters contain high voltage when connected to AC

mains. Installation, start-up and maintenance should be performed by qualified
personnel only. Failure to comply could result in death or serious injury.

• UNINTENDED START. When the frequency converter is connected to AC mains, the

motor may start at any time. The frequency converter, motor, and any driven
equipment must be in operational readiness. Failure to comply could result in death,
serious injury, equipment, or property damage.

• POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE! Risk of personal injury

when the frequency converter is not properly closed. Before applying power, ensure
all safety covers are in place and securely fastened.

1. Confirm that the input voltage is balanced with 3%. If not, correct voltage imbalance

before proceeding. Repeat this procedure after the voltage correction.

2. Ensure that optional equipment wiring, if present, matches the installation application.
3. Ensure that all operator and start enable devices are in the OFF position. Panel doors

should be closed or cover mounted.

4. Apply power to the unit. DO NOT start the frequency converter at this time. For units

with a disconnect switch, turn to the ON position to apply power to the frequency
converter.

Discharge time

WARNING:
Disconnect and lock out electrical power and wait for the minimum waiting time specified
below. Failure to wait the specified time after power has been removed before
performing service or repair could result in death or serious injury.

Frequency converters contain DC-link capacitors that can remain charged even when the
frequency converter is not powered. To avoid electrical hazards, disconnect:

• AC mains
• Any permanent magnet type motors
• Any remote DC-link power supplies, including battery backups, ups and DC-link

connections to other frequency converters.