Induction motor setup, Pm motor setup, Induction motor setup pm motor setup – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 97

Advertising
background image

5. Use navigation keys to select [0] International or [1] North America as appropriate and

press [OK]. This changes the default settings for a number of basic parameters. See
5.4 International/North American Default Parameter Settings for a complete list.)

6. Press [Quick Menu] on the LCP.
7. Use the navigation keys to scroll to parameter group Q2 Quick Setup and press [OK].

Figure 37: Quick menus

8. Select language and press [OK].
9. A jumper wire should be in place between control terminals 12 and 27. If this is the

case, leave 5–12 Terminal 27 Digital Input at factory default. Otherwise select No
Operation
. For frequency converters with an optional Xylem bypass, no jumper wire is
required.

10. 3–02 Minimum Reference
11. 3–03 Maximum Reference
12. 3–41 Ramp 1 Ramp Up Time
13. 3–42 Ramp 1 Ramp Down Time
14. 3–13 Reference Site. Linked to Hand/Auto* Local

Induction motor setup

Enter the motor data in parameters 1–20/1–21 to 1–25. The information can be found on
the motor nameplate.
1.

1–20 Motor Power [kW] or 1–21 Motor Power [HP]
1–22 Motor Voltage
1–23 Motor Frequency
1–24 Motor Current
1–25 Motor Nominal Speed

Figure 38: Motor setup

PM motor setup

CAUTION:
Only use PM motor with fans and pumps.

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

95