Maximum terminal load (DC-13)

1)

on 45 (NO) (inductive

load)

24 V DC, 0.1 A

Maximum terminal load (AC-1)

1)

on 46 (NC) (resistive

load)

240 V AC, 2 A

Maximum terminal load (AC-15)

1)

on 46 (NC) (inductive

load @ cosϕ 0.4)

240 V AC, 0.2 A

Maximum terminal load (DC-1)

1)

on 46 (NC) (resistive

load)

50 V DC, 2 A

Maximum terminal load (DC-13)

1)

on 46 (NC) (inductive

load)

24 V DC, 0.1 A

Minimum terminal load on 13 (NC), 12 (NO), 46 (NC), 45

(NO)

24 V DC 10 mA, 24 V AC 20 mA

Environment according to EN 60664–1

overvoltage category III/pollution degree 2

1)

IEC 60947 part 4 and 5

The relay contacts are galvanically isolated from the rest of the circuit by reinforced
isolation (PELV).

2)

Overvoltage category II

3)

UL applications 300 V AC 2A

Control card, 10 V DC output

Terminal number

50

Output voltage

10.5 V ±0.5 V

Maximum load

15 mA

The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-
voltage terminals.

Control characteristics

Resolution of output frequency at 0–590 Hz

± 0.003 Hz

Repeat accuracy of Precise start/stop (terminals 18, 19)

≤± 0.1 ms

System response time (terminals 18, 19, 27, 29, 32, 33) ≤ 2 ms
Speed control range (open loop)

1:100 of synchronous speed

Speed control range (closed loop)

1:1000 of synchronous speed

Speed accuracy (open loop)

30–4000 rpm: error ±8 rpm

Speed accuracy (closed loop), depending on resolution of

feedback device

0–6000 rpm: error ±0.15 rpm

All control characteristics are based on a 4–pole asynchronous motor

Environment

Enclosure

IP20 Open, NEMA 1, NEMA12, NEMA 4X

Vibration test

1.0 g

Maximum relative humidity

5% 93% (IEC 72133) Class 3K3 (non-condensing) during

operation

Aggressive environment (IEC 60068243) H

2

S test

class Kd

Ambient temperature

3)

Maximum 50°C (24hour average maximum 45°C)

Minimum ambient temperature during full-scale

operation

0°C

Minimum ambient temperature at reduced performance 10°C
Temperature during storage/transport

25 to +65/70°C

Technical Specification

132

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL