General technical data – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 130

Advertising
background image

• LCP and typical control card power consumptions are included. Further options and

customer load may add up to 30 W to the losses. (Though typically only 4 W extra for
a fully loaded control card or options for slot A or slot B, each)

• Although measurements are made with state of the art equipment, some

measurement inaccuracy must be allowed for (±5%).

6) A2+A3 may be converted to IP21 using a conversion kit. (See Pricebook for conversion
kit order numbers.)
7) B3+B4 and C3+C4 may be converted to IP21 using a conversion kit. (See Pricebook for
conversion kit order numbers.)

General technical data

Mains supply

Supply terminals

L1, L2, L3

Supply voltage

200–240 V ±10%

Supply voltage

380–480 V/525–600 V ±10%

Supply voltage

525–690 V ±10%

Mains voltage low/mains drop-out: During low mains voltage or a mains drop-out, the
drive continues until the intermediate circuit voltage drops below the minimum stop level,
which corresponds typically to 15% below the frequency converter’s lowest rated supply
voltage. Power-up and full torque cannot be expected at mains voltage lower than 10%
below the frequency converter’s lowest rated supply voltage.

Supply frequency 50/60 Hz ±5%

Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
True power factor (λ)

≥ 0.9 nominal rated load

Displacement Power Factor (cos φ)

near unity (> 0.98)

Switching on input supply L1, L2, L3 (power-ups) ≥ 10

HP

maximum 2 times/minute

Switching on input supply L1, L2, L3 (power-ups) 15-100

HP

maximum 1 time/minute

Switching on input supply L1, L2, L3 (power-ups) ≥ 125

HP

maximum 1 time/2 minutes

Environment according to EN60664–1

overvoltage category III/pollutin degree 2

The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS
symmetrical Amperes, 240/500/600/690 V maximum.

Motor output (U, V, W)

Output voltage

0–100% of supply voltage

Output frequency (1.5 - 125 HP)

0–590 Hz

Output frequency (110–250 kW)

0–590

1)

Hz

Switching on output

Unlimited

Ramp times

1–3600 s

1)

Voltage and power dependent

Torque characteristics

Starting torque (constant torque)

maximum 110% for 60 s

1)

Starting torque

maximum 135% up to 0.5 s

1)

Overload torque (constant torque)

maximum 110% for 60 s

1)

Technical Specification

128

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

Advertising