Motor connection, Figure 5: basic electrical connection, Electrical installation 20 aquavar – Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 22: Intelligent pump controller instruction manual

Advertising
background image

*

91 (L1)
92 (L2)
93 (L3)

PE

88 (-)
89 (+)

50 (+10 V OUT)

53 (A IN)

54 (A IN)

55 (COM A IN)

0/4-20 mA

12 (+24V OUT)

13 (+24V OUT)

18 (D IN)

20 (COM D IN)

15mA

200mA

(U) 96
(V) 97

(W) 98

(PE) 99

(COM A OUT) 39

(A OUT) 42

0/4-20 mA

03

0-10Vdc

+10Vdc

0-10Vdc
0/4-20 mA

240Vac, 2A

24Vdc

02

01

05

04

06

240Vac, 2A

24V (NPN)
0V (PNP)

0V (PNP)

24V (NPN)

19 (D IN)

24V (NPN)
0V (PNP)

27

24V

0V

(D IN/OUT)

0V (PNP)

24V (NPN)

(D IN/OUT)

0V

24V

29

24V (NPN)
0V (PNP)

0V (PNP)

24V (NPN)

33 (D IN)

32 (D IN)

1
2

ON

A53/S201

ON

2

1

A54/S202

ON=0-20mA
OFF=0-10V

95

400Vac, 2A

P 5-00

(R+) 82

(R-) 81

37 (D IN)

+

-

+

-

130BA544.12

(P RS-485) 68

(N RS-485) 69

(COM RS-485) 61

0V

5V

S801

RS-485

RS-485

2

1

ON

BUS TER./S801

3 Phase

power

input

DC bus

Switch Mode

Power Supply

Motor

Analog Output

Interface

relay1

relay2

ON=Terminated
OFF=Open

Brake

resistor

(NPN) = Sink

(PNP) = Source

Figure 5: Basic electrical connection

Motor connection

WARNING:
INDUCED VOLTAGE. Run output motor cables from multiple frequency converters
separately. Induced voltage from output motor cables run together can charge
equipment capacitors even with the equipment turned off and locked out. Failure to run
output motor cables separately could result in death or serious injury.

Be sure the following are adhered to:

• For maximum wire sizes see Power-dependent Specifications.
• Comply with local and national electrical codes
• Motor wiring knockouts or access panels are provided at the base of IP21 and higher

(NEMA 1/12) units

• Do not install power factor correction capacitors between the frequency converter

and the motor

• Do not wire a starting or pole-changing device between the frequency converter and

the motor

• Connect the 3–phase motor wiring to terminals 96 (U), 97 (V), and 98 (W)
• Ground the cable in accordance with grounding instructions provided
• Torque terminals in accordance with the informations provided in Connection

tightening torques.

• Follow motor manufacturer wiring requirements

Electrical Installation

20

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL