A common use of two pressure transducer feedback signals is to take the difference
between the signals to create a differential pressure transducer. To implement a
differential pressure transducer with 2 pressure transducers, set parameter [20-20]
Feedback Function to Difference. The controller will calculate the feedback value as
Feedback 1 Source [20-00] – Feedback 2 Source [20-03]. Be sure to set all unused
feedback sources to No Function (parameters 20-00, 20-03 or 20-06). The parameter
listing that follows shows how to configure the additional transducer.

• Analog inputs can be configured using the Start-Up Genie.
• Be sure to properly set the analog input configuration switch prior to using the analog

input. Refer to the Analog input configuration (Switches A53 and A54) for details.

Figure 21: Connections for adding 4–20 mA transducer feedback to AI 54

Figure 22: Connections for adding 0–10 V transducer feedback to AI 54

In order to set up the controller for closed loop control based on the feedback from an
external transducer, set the following parameters:

Table 6: Parameter settings to enable an additional transducer on AI 54

Parameter Number

Parameter Description

Set To

6-24*

Terminal 54 Low Ref./Feedb. Value

Minimum transducer feedback value.

For example, for a 0-300psi

transducer, set to 0.

6-25*

Terminal 54 High Ref./Feedb. Value

Maximum transducer feedback

value. For example, for a 300psi

transducer, set to 300.

6-27*

Terminal 54 Sensor Fault

Enabled

20-03

Feedback 2 Source

Analog Input 54*

20-05

Feedback 2 Source Unit

Units for the second feedback source.

For a differential pressure transducer,

use the same units as found in 20-02,

psi is default

Electrical Installation

36

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL