Xylem IM255 AQUAVAR Intelligent Pump Controller User Manual

Page 48

Advertising
background image

QStop

The motor is decelerating using 3–81 Quick Stop Ramp

Time.

Quick stop inverse was chosen as a function for a

digital input (parameter group 5–1* Digital Inputs).

The corresponding terminal is not active.

• The quick stop function was activated via serial

communication.

Ramping

The motor is accelerating/decelerating using the active

Ramp Up/Down. The reference, a limit value or a

standstill is not yet reached.

Ref. high

The sum of all active references is above the reference

limit set in 4–55 Warning Reference High.

Ref. low

The sum of all active references is below the reference

limit set in 4–54 Warning Reference Low.

Run on ref.

The controller is running in the reference range. The

feedback value matches the setpoint value.

Run request

A start commend has been given, but the motor is

stopped until a run permissive signal is received via

digital input.

Running

The motor is driven by the controller.

Sleep mode

The energy saving function is enabled. This means that at

present the motor has stopped, but that it will restart

automatically when required.

Speed high

Motor speed is above the value set in 4–53 Waning

Speed High.

Speed low

Motor speed below the value set in 4–52 Warning Speed

Low.

Standby

In Auto On mode, the controller will start the motor with

a start signal from a digital input or serial

communication.

Start delay

In 1–71 Start Delay, a delay starting time was set. A start

command is activated and the motor will start after the

start delay time expires.

Start fwd/rev

Start forward and start reverse were selected as functions

for two different digital inputs (parameter group 5–1*

Digital Inputs). The motor will start in forward or reverse

depending on which corresponding terminal is activated.

Stop

The controller has received a stop command from the

LCP, digital input or serial communication.

Trip

An alarm occurred and the motor is stopped. Once the

cause of the alarm is cleared, the controller can be reset

manually by pressing [Reset] or remotely by control

terminals or serial communication.

Trip lock

An alarm occurred and the motor is stopped. Once the

cause of the alarm is cleared, power must be cycled to the

controller. The controller can then be reset manually by

pressing [Reset] or remotely by control terminals or serial

communication.

LCP parameters

The display configuration shown above represents the default settings. Items 2-6 can be
adjusted to display other values. To display other values, modify parameters 0-20, 0-21,
0-22, 0-23 or 0-24 which correspond to 2, 3, 4, 5 and 6 respectively.

Electrical Installation

46

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL