Parameter number

Parameter Name

Default Value

Parameter Description

20-93

PID Prop Gain

5

Proportional correction gain

for PID controller.

Increasing this value will

produce a faster system

response. CAUTION:

Increasing this value too

high can make the system

unstable and produce

severe oscillations.

20-94

PID Integration Time

3.3 s

Integration time for the PID

controller. Increasing this

value will produce a slower

system response. CAUTION:

Decreasing this value too

low can make the system

unstable and produce

severe oscillations.

Start-Up Genie

This controller is equipped with a Start-Up Genie which allows the user to easily configure
the controller for various pump control applications. The Genie configures parameters
that are based on the selections that are made by the user. The Genie allows the user to
configure the motor, application type, inputs, outputs, pump protection features, flow
compensation, and communications. The application types include single pump, constant
slave, duplex control, speed control, and test run mode. See the Setup and
Commissioning section for details.

Main menu

The parameters in the Main Menu are grouped by category. Note that some groups are
not visible unless the appropriate option card is installed. The parameter groups in the
Main Menu are shown below.

Parameter Group

Parameter Group Name

0

Operation/Display

1

Load and Motor

2

Brakes

3

Reference/Ramps

4

Limits/Warnings

5

Digital In/Out

6

Analog In/Out

8

Comm. and Options

9

Profibus*

10

CAN Fieldbus*

11

LonWorks*

13

Smart Logic

14

Special Functions

15

Drive Information

16

Data Readouts

18

Info & Readouts

20

Drive Closed Loop

21

Ext. Closed Loop

22

Appl. Functions

Operation

Aquavar

®

Intelligent Pump Controller INSTRUCTION MANUAL

61

Advertising