NOTE: Check that the chosen supply voltage follows the specification of the thermistor
element.
Summary

Input
Digital/analog

Supply Voltage V
Cut-out Values

Threshold
Cut-out Values

Digital

24

< 6.6kΩ — > 10.8kΩ

Digital

10

< 800kΩ — > 2.7kΩ

Analog

10

< 3.0kΩ — > 3.0kΩ

With the Torque limit feature the motor is protected from being overloaded independent
of the speed. With the ETR the motor is protected from being overheated and there is no
need for any further motor protection. That means when the motor is heated up the ETR
timer controls how long the motor can be operated at the high temperature before it is
stopped in order to prevent overheating. If the motor is overloaded without reaching the
temperature where the ETR turns off the motor, the torque limit will protect the motor
from being overloaded.
The ETR function is activated in 1-90 Motor Thermal Protection and is controlled in 4-16
Torque Limit Motor Mode. The time before the torque limit warning trips the drive is set in
14-25 Trip Delay at Torque Limit.