Warning/Alarm

Description

Cause

Remedy

15 — Hardware mismatch

A fitted option is not operational

with the present control board

hardware or software.

Record the value of the following

parameters and contact your

Xylem supplier:

• [15–40] FC Type
• [15–41] Power Section
• [15–42] Voltage
• [15–43] Software Version
• [15–45] Actual Typecode

String

• [15–49] SW ID Control Card
• [15–50] SW ID Power Cord
• [15–60] Option Mounted
• [15–61] Option SW Version

16 — Short circuit

There is a short circuit in the motor

or motor wiring.

Remove power to the frequency

converter and repair the short

circuit.

17 — Control word timeout

There is no communication to the

frequency converter.
The warning will only be active

when [8–04] Control Timeout

Function is NOT set to [0] OFF.

If [8–04] Control Timeout Function

is set to Stop and Trip, a warning

appears and the frequency

converter ramps down until it

stops then displays an alarm.

Check connections on the series

communication cable.
Increase [8–03] Control Timeout

Time
Check operation of the

communication equipment
Verify proper installation based on

EMC requirements.

18 — Start failed

The speed has not been able to

exceed [1–77] Compressor Start

Max Speed [RPM] during start

within the allowed time. (set in [1–

79] Compressor Start Max Time to

Trip).

This may be caused by a blocked

motor.

23 — Internal fan fault

The fan warning function checks if

the fan is running. The fan

warning can be disabled on [14–

53] Fan Monitor.

Check for proper fan operation.
Cycle power to the frequency

converter and check that the fan

operates briefly at startup.
Check the sensors on the heatsink

and control card.

24 — External fan fault

The fan warning function checks if

the fan is running. The fan

warning can be disabled on [14–

53] Fan Monitor.

Check for proper fan operation.
Cycle power to the frequency

converter and check that the fan

operates briefly at startup.
Check the sensors on the heatsink

and control card.

25 — Brake resistor short circuit

The brake resistor is monitored

during operation. If a short circuit

occurs, the brake function is

disabled and the warning appears.

The frequency converter is still

operational but without the brake

function.

Remove power to the frequency

converter and replace the brake

resistor (see [2–15] Brake Check).