Yokogawa digitalYEWFLO (DY) User Manual

Page 112

Advertising
background image

<13. GENERAL SPECIFICATIONS>

13-2

IM 01F06A00-01EN

Weight:

Refer to Section 13.7 “External Dimensions”.

Mounting:

Integral type and Remote type detector:

Flange mounting or wafer mounting by
fl ange adjacent to the pipeline.

Remote type converter: 2 inch pipe mounting.

Electrical Specifi cations

Note*: Pulse output,alarm output and status output use the

common terminal, therefore these functions are not
used simultaneously.

Output Signal (): Dual Output (Both Analog

and Transistor contact output can be obtained
simultaneously). In this ca

se refer to Section

3.2 “Piping Precautions” for power supply
and pulse output wiring.

Analog: 4 to 20 mA DC, 2-wire system.
Transistor Contact Output*:

Open collector, 3-wire system.
Pulse,alarm,status output are selected by
parameter setting.
Contact rating: 10.5 to 30 V DC, 120 mA DC
Low level: 0 to 2 V DC. (refer to Figure 13.3)

Communication Requirements:

Communication Signal:

BRAIN or HART communication signal
(superimposed on a 4 to 20 mA DC signal)

Note: HART is a registered trademark of the HART

Communication Foundation.

Conditions of Communication Line:

Load Resistance:
250 to 600

Ω(including cable resistance).

Refer to Figure 13.2.
Supply Voltage:
16.4 to 42 V DC for digital communications
BRAIN and HART protocols. (16.4 to 30 V DC
for intrinsically safe type).
Refer to Figure 13.2.

BRAIN:

Space from other Power Line: 15cm or more
(Parallel wiring should be avoided.)
Communication Distance:
Up to 2 km,when polyethylene insulated
PVC-sheathed cables (CEV cables) are used.
Communication distance varies depending on
type of cable used and wiring.
Load Capacitance: 0.22

μF or less

Load Inductance: 3.3 mH or less
Input Impedance Communicating Device:
10 k

Ω or more at 2.4 kHz.

Selection of HART 5/ HART 7

Output Signal

Code

-E

-J

Ordering

Information

Specify “5”

Specify “7”

HART Protocol

Revision

HART 5

HART 7

Selection

guide

Requirement

for HART 7

functionarlity

NO

YES

Be sure to

confi rm the

protocol

revision

of the HART

confi guration

tool

shown in *2.

Other

conditions

Not

available

to switch to

HART 7
protocol

after

delivery.

Available to

switch to HART

7 protocol after

delivery by

userconfi guration.

Remarks

*1

*2

*2

*1: “-E” is HART5 exclusive model and will be terminated. “-J”

is recommended for HART communication.

*2: HART protocol revision for the device and HART

confi guration tool HART7 communication is supported
by FieldMate R2.02 or later.

HART protocol revision and availability

Protocol revision

supported by HART

confi guration tool

5

7

DY or DYA HART 5

Available

Available

DY or DYA HART 7

Not Available

Available

Note: Protocol revision supported by HART confi guration tool must

be the same or higher than that of the digitalYEWFLO.

Functions:

Damping Time Constant:

0 to 99 Sec (63% response time)

Note: Delay time is 0.5 Sec.

Analog output circuit time constant is 0.3 Sec.

Pulse Output Function*:

Pulse output is selected from scaled pulse,
unscaled pulse, frequency (number of pulses
output per second at 100% of output).
Pulse frequency: Max 10 kHz
Duty cycles: Approx.50% (1:2 to 2:1)

Self-diagnostics and Alarm Output *:

In case alarm (over range output signal,
EEPROM error, vibration noise, abnormal fl ow
such as clogging, bubble) occurs, an alarm
signal is output and indicated.
The alarm signal output goes from close(ON) to
open(OFF) during alarming.

Analog Output Function:

Analog output is selected from fl owrate and
temperature value when option code /MV is
selected.