<6. PARAMETERS>

6-13

IM 01F06A00-01EN

(3) Item C : BASIC SETUP

These items are for the basic parameters with
setting before shipment.
The parameters which are set in B are not
necessary to set in C.
A value in “( )” is the data corresponding to
indicator.

The parameters, C20 to C50, are not
indicated when option code “/MV” is
selected and parameter item is selected in
F10 except “Monitor only” or “Not Use”.

[C10: TAG NO] Tag. No

Set Tag. No. (16 characters)
Available characters are as follows.

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z a
b c d e f g h i j k l m n o p q r s t u v w x y z 0 1 2 3 4 5 6 7
8 9 . SPACE / - , +

*

) (

& % $ # “ !

F0603.ai

[C20:FLUID] Flowrate unit

Set the fl owrate unit below.

Item

Description

LIQUID : Volume

(0) Volumetric fl ow of Iiquid measuring

GAS/STEAM : Volume (1) Volumetric fl ow of gas or steam

measuring

LIQUID : Mass

(2) Mass fl ow of liquid measuring

GAS/STEAM : Mass (3) Mass fl ow of gas or steam

measuring

GAS : STD/Normal

(4) Volumetric fl ow at Standard

condition

The following items should be done in case
of which “C20” is “LIQUID : Volume” or
“GAS/STEAM : Volume”.

[C22:VOLUME UNIT] Volumetric unit

Select the unit of volumetric fl ow from m

3

(0),

k m

3

(1), l(2), cf(3), m cf(4), k cf(5), USgal(6),

k USgal(7), UKgal(8), k UKgal(9), bbl(10),
m bbl(11), k bbl(12).

The following items should be done in case
of which “C20” is “LIQUID: Mass” or “GAS/
STEAM : Mass”

[C25:DENSITY UNIT] Density Unit of Flow
measurement

Select the unit of density from kg/m

3

(0), lb(1), lb/

USgal(2), lb/UKgal(3).

[C26:DENSITY f] Density at normal
operation conditions

Set the density value of the fl uid at operating
condition for mass fl ow unit.

[C27:MASS UNIT] Mass fl owrate unit

Select the mass fl owrate unit from kg(0), t(1), lb(2),
k lb(3).

The following item should be done in case
of which “C20” is “GAS/STEAM : Volume”.

[C30:TEMP UNIT] Fluid temperature unit at
operating conditions

Select temperature unit at operating condition from
“degC (0), degF (1)”.

[C31:TEMP f] Fluid temperature at
operating conditions

Set fl uid temperature at operating condition.

The following items should be done in case
of which “C20” is “GAS/STD : Normal”.

[C32:TEMP b] Fluid temperature at
standard/normal conditions

Set the values of Fluid temperature at standard
condition.

[C33:PRESS UNIT] Pressure unit

Select the unit of pressure.

BRAIN

HART

MPa abs

(0) MPa abs

(0)

kPa abs

(1) kPa abs

(1)

bar abs

(2) kg/cm

2

a

(2)

kg/cm

2

a

(3) bar abs

(3)

psia (4) psia

(4)

[C34:PRESS f] Absolute pressure at
operating conditions

Set the absolute pressure at operating condition.

[C35:PRESS b] Absolute pressure at
standard/normal condition

Set the absolute pressure at normal condition.

[C36:DEVIATION] Deviation factor

Set deviation factor.

[C37:STD/NOR UNIT] Volumetric unit at
normal conditions

Select volumetric unit at normal condition from
Nm

3

(0), k Nm

3

(1), M Nm

3

(2), Nl(3), Sm

3

(4),

k Sm

3

(5), M Sm

3

(6), Sl(7), scf(8), k scf(9), M scf(10).

N: Normal
S: Standard