<13. GENERAL SPECIFICATIONS>

13-16

IM 01F06A00-01EN

Table 13.9

Range of Measurable Air Flow Rate at Selected Process Pressures

Model Code

Flow

Rate

Limits

Minimum and Maximum Measurable Flow Rate in Nm

3

/h

0 MPa

0.1 MPa 0.2 MPa 0.4 MPa 0.6 MPa 0.8

MPa

1 MPa 1.5 MPa 2

MPa

2.5

MPa

DY015

DY025

/R1

DY040

/R2

min. 4.8(11.1) 6.7(11.1) 8.2(11.1) 10.5(11.1)

12.5

16.1

19.7

28.6

37.5

46.4

max.

48.2

95.8

143

239

334

429

524

762

1000

1238

DY025

DY040

/R1

DY050

/R2

min. 11.0(19.5) 15.5(19.5)

19.0(19.5)

24.5

29.0

33.3

40.6

59.0

77.5

95.9

max.

149

297

444

739

1034

1329

1624

2361

3098

3836

DY040

DY050

/R1

DY080

/R2

min. 21.8(30.0)

30.8

37.8

48.7

61.6

79.2

97

149

184

229

max.

356

708

1060

1764

2468

3171

3875

5634

7394

9153

DY050

DY080

/R1

DY100

/R2

min. 36.2(38.7)

51

62.4

80.5

102

131

161

233

306

379

max.

591

1174

1757

2922

4088

5254

6420

9335

12249 15164

DY080

DY100

/R1

DY150

/R2

min.

70.1

98.4

120

155

197

254

310

451

591

732

max.

1140

2266

3391

5642

7892

10143 12394 18021 23648 29274

DY100

DY150

/R1

DY200

/R2

min.

122

172

211

272

334

442

540

786

1031

1277

max.

1990

3954

5919

9847

13775 17703 21632 31453 41274 51095

DY150

DY200

/R1

min.

268

377

485

808

1131

1453

1776

2583

3389

4196

max.

4358

8659

12960

21559

30163 38765 47365 68867 90373 111875

DY200

min.

575

809

990

1445

2202

2599

3175

4617

6059

7501

max.

7792

15482

23172

38549

53933 69313 84693 123138 161591

200046

DY250

min.

1037

1461

1788

2306

3127

4019

4911

7140

9370

11600

max.

12049

23939

35833

59611

83400 107181 130968

190418

249881

309334

DY300

min.

1485

2093

2561

3303

4479

5756

7033

10226 13419 16612

max.

17256

34286

51317

85370

119441 153499

187556

272699

357856

443017

DY400

min.

2790

3933

4812

7020

9821

12622

15422

22424

29426

36427

max.

28378

56385

84391

140405

196418 252432 308445 448479 588513 728547

(1) Listed fl ow rate is at standard conditions STP (0°C. 1atm).
(2) Listed gauge pressure is at process temperature of 0°C.
(3) Maximum fl ow rate is the lower of 80m/s.
(4) Minimum fl ow rate: (value) is the lower limit of the accuracy range.

Advertising