<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-6

IM 01F06A00-01EN

a. Burst Command

Select the transmission data at Burst Command
parameter.

Burst Command

Command parameter

Cmd1:PV

Variable assigned to PV

Cmd2:% range/current % range/current (Percent of rang,

Loop current)

Cmd3:Dyn vars/current Process vars/current (Loop current,

PV, SV, TV, QV)

Cmd9:Device vars
w/Status

Process vars/% range/current
Mapping by user

Cmd33:Device
Variables

Process vars/% range/current
Mapping by user

Cmd48:Read Additional
Device Status

Self diagnosis information

b. Burst Variable Code

This parameter is possible to be set when Burst
Command
is Cmd9:Device vars w/Status (up to
eight items) and Cmd33: Device Variables (up to
four items).
Set device variables to a bare minimum to avoid to
get the communication time longer.

• Procedure to call up the display

DD (HART 7)
DTM (HART 7)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

Burst Condition

→ Burst Message1, 2 or 3

→ Burst Device Variables →
Burst Variable Code

Display Item

Contents

Flowrate

Flowrate

Total

Total fl ow

Temperature

Temperature

Density

Density

%rnge

Select the % output

Loop current

Select the output current

PV

Select the PV value

SV

Select the SV value

TV

Select the TV value

QV

Select the QV value

Not use

c. Update Period and Max Update Period

Set to Update Period and MaxUpdate Period.
Set greater value of update period than a value
which is set in each process value.
For Update Period, set the value that is smaller
than Max Update Period.

• Procedure to call up the display

DD (HART 7)
DTM (HART 7)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

Burst Condition

→ Burst Message1, 2

or 3

→ Set Burst Period →

Update Period
/Max Update
Period

0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min

d. Burst Msg Trigger Mode

Set The Burst Msg Trigger Mode from the
parameters shown below.
When Burst Msg Trigger Mode is Window, Rising
or Falling, set the Burst Trigger Level.

• Procedure to call up the display

DD (HART 7)
DTM (HART 7)

[Root Menu]

→ Detailed setup →

Confi gure outputs

→ HART output →

Burst Condition

→ Burst Message1, 2 or 3

→ Set Burst Trigger →

Display Item

Contents

Continuous

Burst Message is transmitted contiuously.

Window

It detects that the absolute value of the
amount of change of a device variable value
became beyond the preset value of Burst
Trigger Level, and transmits.

Rising

It detects that the device variable value
became beyond the preset value of Burst
Trigger Level, and transmits.

Falling

It detects that the device variable value
turned into below the preset value of Burst
Trigger Level, and transmits.

On-change

It detects that the device variable value
changed and transmits.

*1: Check transmitting conditions with the cycle set as Update

Period, and when it corresponds to conditions, they transmit.

Moreover, even if it does not correspond to conditions, it
transmits compulsorily with the cycle set up by Max Update
Period.