<4. WIRING>

4-3

IM 01F06A00-01EN

Table 4.1 (a) The wiring example for the analog and pulse and status, alarm output.

Connection

Description

Analog Output

In this case, Communication
is possible (up to a distance
of 2km when a CEV cable is
used.)

digitalYEWFLO Electrical Terminal

250

Ω

24V DC

+

Distributor

PULSE

SUPPLY

+

+

Pulse Output

In this case, No
communication is possible.

This supply voltage requires
a power sourse with a
maximum output current of
no less than E/R+25mA.

R

E

digitalYEWFLO Electrical Terminal

Use the Three-wire shielded cable.

Electric counter

*1

*2

Shielded Cable

PULSE

SUPPLY

+

+

Status Output

Alarm Output

In this case,
No communication is
possible.

Use the Three-wire shielded cable.

Shielded Cable

PULSE

SUPPLY

+

+

Magnetic

valve

AC power supply

External Power supply
30V DC, 120mA max
(Contact Rating)

digitalYEWFLO Electrical Terminal

E

Relay

*1: To avoid the infl uence of external noise, use an electric counter which fi ts to the pulse frequency.
*2: Resistor is not necessary in case of an electric counter which can receive contact pulse signal directly.