<14. EXPLOSION PROTECTED TYPE INSTRUMENT>

14-6

IM 01F06A00-01EN

(5) Installation Diagram

Intrinsically Safe (and WARNING)

F1404.ai

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

+

-

+

[Remote type]

DYA (converter)

SUPPLY

PULSE

A

B

T (*1)

C

A

B

T

DY (flowmeter)

SUPPLY

PULSE

Safety barriers

Safety barriers

[Integral type]

DY-N (flowmeter)

Hazardous Location

Class I, II, III, Division 1,
Groups A, B, C, D, E, F and G,
and Class I, Zone 0, Group IIC

Non Hazardous
Location

DYC: Signal cable

(*1) Wire for T terminal
With temperature sensor type : installed
Without temperature sensor type: not installed

Electrical parameters of vortex flowmeter (DY) and vortex flow
converter (DYA).
Vmax=30V Imax=165mA Pi=0.9W
Ci=12nF

Li=0.15mH

Installation requirement between flowmeter, converter and
Safety Barrier
Vt or Voc ” Vmax It or Isc ” Imax Po ” Pi

Ca

• Ci+Ccable

La • Li+Lcable

Vt, Voc, It, Isc, Voc, Ca and La are parameters of barrier.

WARNING

• In any safety barrier used output current

must be limited by a resistor ‘R’ such that
Isc=Voc/R.

• Any Single FM Approved Barrier of multiple

barriers FM Approved for this confi guration
who’s parameters meet the above
installation requirements.

• Input voltage of the safety barrier must be

less than 250Vrms/Vdc.

• Installation should be in accordance with

National Electrical Code, ANSI /NFPA70.

• Dust-tight conduit seal must be used when

installed in class II and III environments.

• Do not alter drawing without authorization

from FM.

Nonincendive (and WARNING)

Hazardous Location

Non Hazardous
Location

Class I, II, Division 2,
Groups A, B, C, D, F and G,
Class III, Division 1, and
Class I, Zone 2, Group IIC

[Integral type]

[Remote type]

DY (flowmeter)

SUPPLY

PULSE

+

+

+

+

+

+

Power

Supply

Receiver

DY (converter)

DY-N (flowmeter)

SUPPLY

PULSE

+

+

+

+

+

+

Power

Supply

Receiver

A

B

T

C

A

B

T

(*1)

DYC: Signal cable

(*1) Wire for T terminal
With temperature sensor type : installed
Without temperature sensor type: not installed

Non-incendive field wire parameters of vortex flowmeter (DY)
and vortex flow converter (DYA).
Vmax=30V

Imax=165mA

Pi=0.9W

Ci=12nF

Li=0.15mH

Installation requirement between flowmeter, converter and
general purpose equirement.
Vt or Voc ” Vmax It or Isc ” Imax Po ” Pi
Ca • Ci+Ccable La • Li+Lcable

Vt, Voc, It, Isc, Po, Ca and La are nonincendive field
wire parameters of general purpose equipment.

F1405.ai

WARNING

• The general purpose equipment must be

FM approved with Nonincendive fi eld wiring
parameter which meet the above installation
requirements.

• Installation should be in accordance with

National Electric Code, ANSI/NFPA70.

• Dust-tight conduit seal must be used when

installed in class II and III environments.

• Do not alter drawing without authorization

from FM.