2 burst mode, 2 burst, Mode – Yokogawa digitalYEWFLO (DY) User Manual

Page 76: 1) burst message

Advertising
background image

<9. OPERATION VIA HART CONFIGURATION TOOL (HART 7)>

9-4

IM 01F06A00-01EN

Table 9.1

Burst parameters

Command parameter

Burst Command

Burst Msg Trigger

Mode

Burst Trigger Source Burst Trigger Units

PV
(fl ow rate)

Cmd1:PV

Continuous

Window

PV

Depends on the
assigned variable to
PV

Rising
Falling
On-change

% range/current
(Percent of range, Loop current)

Cmd2: % range/
current

Continuous

Window

% range

%

Rising
Falling
On-change

Process vars/current
(Loop current, PV, SV, TV, QV)

Cmd3:Dyn vars/
current

Continuous

Window

PV

Depends on the
assigned variable to
PV

Rising
Falling
On-change

Process vars/%range/current with status

*1

(Select from fl ow rate, total fl ow,
temperature, density, percent of range,
loop current, PV, SV, TV, and QV)

*2

Cmd9:Device vars w/
Status

Continuous

Window

Top of Burst Device
Variables

Depends on maapping

Rising
Falling
On-change

Process vars/%range/current
(Select from fl ow rate, total fl ow,
Temperature, Density, percent of range,
loop current, PV, SV, TV, and QV)

*2

Cmd33:Device
Variables

Continuous

Top of Burst Device
Variables

Depends on the
assigned variable to
Burst Device Variable

Window
Rising
Falling
On-change

Self diagnosis information

Cmd48:Read
Additional Device Status

Continuous

On-change

All status

*1: Output the data with time and status.
*2: Select at Burst Device Variables

Update time period of each measurement value is
as follows;

• Flow rate: Flow rate Update time period
• Total: Total Update time period
• Temperature: Temperature Update time period
• Density: Density Update time period

9.10.2 Burst Mode

When the Burst mode is enabled, the device
continuously sends up to three data listed in Table
9.1.
When the Burst mode is set to “Wired HART
Enabled”, the device continuously sends alarm
signal also.
Refer to Subsection 9.10.3 “Event Notifi cation” for
detail.
When changing the setting of Burst mode, set “Off”
to the Burst mode. Default setting is “Off”.

(1) Burst Message

The parameters for Burst Message are as
follows.

• Transmit data: command parameters of Burst

Command

• Device

variables:

• Update

period

• Transmit condition: choice in Burst Msg Trigger

Mode
Refer to Table 9.1 for the combination between
command parameter and transmit condition.
[Root Menu]

→ Detailed setup → Confi gure

outputs

→ HART output → Burst Condition →

Burst Message1, 2, 3

→ Burst command

NOTE

• In case of Burst Mode setting change, confi rm

Burst Mode parameter is OFF.

• Prioritize to use the 'Burst Message 1'.

Advertising