Warning – Yokogawa digitalYEWFLO (DY) User Manual

Page 153

Advertising
background image

<14. EXPLOSION PROTECTED TYPE INSTRUMENT>

14-2

IM 01F06A00-01EN

(Integral Type Vortex Flowmeter)

Temperature Class

Ambient

Temperature

Process

Temperature

T4 60°C

135°C

T3 60°C

200°C

T2* 60°C

300°C

T1* 60°C

450°C

*: Use /HT version above 250°C

(Remote Type Vortex Flow Detector)

Temperature Class

Ambient

Temperature

Process

Temperature

T4 80°C

135°C

T3 80°C

200°C

T2* 80°C

300°C

T1* 80°C

450°C

*: Use /HT version above 250°C

Electrical data:

Supply and Output Circuit
(SUPPLY + and -, PULSE + and -);
Maximum Input Voltage Ui: 30 V
Maximum Input Current Ii: 165 mA
Maximum Input Power Pi: 0.9 W
Internal Capacitance Ci: 6nF
Internal Inductance Li: 0.15mH

For connection of DYA to DY-N:
Maximum Cable Capacitance: 160nF

Electrical Connection: ANSI 1/2 NPT female, ISO

M20 X 1.5 female

Special conditions for safe use
1. For process temperatures above 250°C the

fl owmeters of the /HT version must be used.

2. Because the enclosures of the fl ow meters

and the fl ow converter are made of aluminium
alloy, when used in an potentially explosive
atmosphere requiring apparatus of equipment
categoly 1 G, they must be installed so, that even
in the event of rare incidents, an ignition source
due to impact of friction between the enclosure
and iron/steel is excluded.

(2) Installation

WARNING

• All wiring shall comply with local installation

requirements and local electrical code.

• Use the suitable heat-resisting cables (over

90°C) for the digitalYEWFLO Model DY
Series Vortex Flowmeter when the ambient
temperature exceeds 60°C and/or the
process temperature exceeds 200°C.

• Cable glands, adapters and/or blanking

elements shall be of Ex “d” for Ex “d”
installations. They shall be installed so as to
maintain the specifi ed degree of protection
(IP Code) of the fl owmeter.

• Unused apertures shall be closed with

above-mentioned blanking elements (in case
of Ex “d” installations).

The grounding terminals are located on the inside
and outside of the terminal area.
Connect the cable to grounding terminal in
accordance with wiring procedure (1) or (2).

Case

Cable

Screw

(1) Internal grounding terminal

(2) External grounding terminal

Washer

Washer

Cable

Clamp

Screw

F1401.ai

Figure 14.1 Wiring Procedure for Grounding

Terminals for Flameproof