<3. INSTALLATION>

3-9

IM 01F06A00-01EN

Table 3.3 (b) Installation of Flange Type Vortex Flowmeter

Horizontal Installation

Vertical Installation

Use the stud bolts and nuts supplied with the
flowmeter of the user.
The gaskets should be supplied by the user.

Flange type

Description

The inside diameter of the gasket must be
larger than the pipe inner diameter so that it
will not disturb the flow in the pipeline.

F0313.ai

CAUTION

Flow Direction

Flow Direction

Nut

Nut

Stud Bolt

Gasket

Gasket

Flange

Flange

Table 3.3 (c) Installation of Remote Type Converter

Remote type converter

Description

A signal cable (DYC) is used between the
remote type flowmeter and the converter.
The maximum signal cable length is 97.5ft
(30m).

The converter is mounted on a 2-inch (60.5mm outer dia.) stanchion or horizontal
pipe.
Do not mount the converter on a vertical pipe. It makes wiring and maintenance
difficult.
The converter mounting orientation can be changed as illustrated below.

F0314.ai

CAUTION

Nut

Bracket

2-inch Pipe

U-Bolt

Horizontal Pipe Mounting

Stanchion Mounting