5) item e : detector setup – Yokogawa digitalYEWFLO (DY) User Manual

Page 42

Advertising
background image

<6. PARAMETERS>

6-6

IM 01F06A00-01EN

(5) Item E : Detector Setup

These items are for detector that has been already set before.

A value in “( )” is the data corresponding to the indicator.

Item

Name

R / W

Data Range

Unit

Decimal

Point

Remark

Initial
Value

Disp. U / D

(*1)

E00 METER SETUP

Menu E (Detector setup)

E10 NOMINAL SIZE

W 15mm

25mm
40mm
50mm
80mm
100mm
150mm
200mm
250mm
300mm
400mm

(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)

(10)

Selection of Nominal Size

(1)

(*2)

D

L

E20 BODY TYPE

W Standard

High Pressure
Low Flow Unit (1)
Low Flow Unit (2)

(0)
(1)
(2)
(3)

Selection of Body Type

(0)

D

L

E30 SENSOR TYPE

W Standard

High Temperature
Low Temperature

(0)
(1)
(2)

Selection of Sensor Type

(0)

D

L

E40 K-FACT UNIT

W P/l

P/USgal
P/UKgal

(0)
(1)
(2)

Selection of K-factor Unit

(0)

D

L

E41 K-FACTOR

W 0.00001 to 32000

E40

0 to 5

K-factor value of 15 deg C

68.6

D

E50 DETECTOR No.

W 16 characters

Detector number

E60 SELF CHECK

R

GOOD
ERROR

Self-diagnostic message

FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If specifi ed when ordering, it is set to the specifi ed contents.

Advertising